A fire-rated partition or ceiling is not just “thicker drywall”. It is a tested system: a specific board, metal frame, fixings and joint treatment that must be built exactly like the certified specimen. In Singapore, these systems are certified by accredited bodies, not by SCDF, and your QP checks the installation matches.
Below is a photo walkthrough from two of our commercial jobs: a fire-rated ceiling and a fire-rated wall partition. It shows what the work actually looks like on site and what to check before you sign off.
Key facts
- Property type: commercial units (shop and office spaces)
- Work shown: fire-rated ceiling boards on a metal grid, and a fire-rated board wall partition
- Main stages: metal framing, board fixing, joint and screw-head treatment, then finishing
- Who signs off: the Qualified Person (QP) for the fire safety plan, using the product’s Certificate of Conformity
What we found: the job in photos

What we did
On both jobs the sequence was the same: set out and fix the metal frame, fix the fire-rated boards with the specified screws and spacing, treat every joint and screw head, then finish the surface. Pink-faced boards like these are the type commonly used for fire resistance, but the colour alone proves nothing. What matters is that the board, frame and fixings match the certified system.
Why this approach matters
SCDF’s Fire Code treats fire-rated partitions and ceilings as regulated fire safety products. They must be certified by an accredited certification body and built in accordance with the tested specimen, with identical materials. SCDF itself does not endorse or certify products, so be wary of anyone selling a partition as “SCDF-approved”.
A partition that looks finished but uses different boards, wider stud spacing or untreated joints can fail inspection, and then has to be opened up or rebuilt. That is the costly outcome we explain in Fail SCDF inspection? Your partition might not be 1-hour fire rated.
What to check before sign-off
| Check | Why it matters |
|---|---|
| Certificate of Conformity for the exact system | Proves the board, frame and fixings were tested together |
| Board type and thickness match the certificate | A different board changes the fire performance |
| Stud and grid spacing as specified | Wider spacing is a common short cut |
| All joints and screw heads treated | Open joints let fire and smoke through |
| Service openings sealed with rated products | Cables and pipes through the wall are weak points |
Frequently asked questions
Is a fire-rated partition “SCDF-approved”?
No. SCDF sets the requirements but does not certify products. Fire-rated partitions are certified by accredited certification bodies, which issue a Certificate of Conformity for the tested system.
Can I tell a fire-rated board by its pink colour?
Not reliably. Pink is common for fire-resistant boards, but only the product markings and the certificate confirm the board type. Ask your contractor for both.
Do fire-rated ceilings follow the same rules as partitions?
Yes. Fire-rated ceilings are also regulated fire safety products and must be installed exactly as the certified system describes.
What happens if the partition fails inspection?
Usually the affected sections must be opened up and corrected or rebuilt, which delays handover or your fire certificate. Getting the system right first time is far cheaper.
Need a fire-rated partition or ceiling?
WhatsApp 9RENO with your layout or site photos for an assessment. See also our fire-rated partition wall service and fire-rated partitions for containers.